VT460 Smoke, Humidity, & Temperature Sensor
Description
The VT460 Triple sensor is a high-quality smoke detector and humidity, temperature sensor. By connecting VT460 in a CAN daisy chain you can measure parameters in each location of a room or a server rack.
The Dew point is easily calculated using the temperature and humidity parameters of VT460 sensor inside the Vutlan web interface.
CAN devices and sensors can be chained together. Up to 10-32 CAN devices can be connected in a chain.
RH accuracy is ± 3%, temperature accuracy is ± 0.5°C.
Use cases
The VT460 Sensor is used for:
- Data Centers: In data centers housing expensive equipment, the VT460 can monitor smoke and heat, which are critical indicators of fire risk.
- Industrial Facilities: In factories and processing plants, the VT460 can monitor smoke emissions from equipment or during manufacturing processes.
Specifications
Device type:
CAN bus device
Used for:
Smoke, fire, temperature, humidity detection
Type:
Photoelectric
Network Interface:
CAN open
Inputs/Outputs:
6P4C RJ12/RJ12 ports
Daisy chain:
Can be connected in a chain with other CAN bus devices.
Operating temperature:
-10° C to +80° C
Operating humidity:
Min. 5% - Max. 95% (Non-Condensing)
Power consumption:
100 mW
Max. distance from the unit:
225 meters
Status Indicators:
Operation and configuration LEDs
Maximum height:
6 meters
Mounting possibilities:
On the сeiling, in a server rack. Bracket included.
TR switch:
Activate if the unit is the last unit in a CAN bus chain.
Manufactured in:
Slovak Republic, E.U.
HS Code:
8531 10 300
GTIN:
8588009886273




Previous
Next
Sensor features
Logic schemes
Logical schemes are used to set automatic actions in response to events occurring in the system.
Dashboard view
The monitoring interface can be customized for each user.
There are widgets with multifunctional graphs and gauges.
Thresholds
Each sensor has 5 alarm thresholds for logical control and notifications.
Graphs and Logging
Vutlan supports recording to SD card and USB stick.
Data from the entire system loaded with sensors is stored for up to 3 years.


Previous
Next
Connecting CAN sensors
You can connect multiple CAN devices to a CAN bus chain.
Each VT408 unit in the CAN bus chain adds 8 analog sensors. Each VT440 unit adds 32 or 64 dry contact inputs to the system.
An additional CAN12V-1A power supply is only required if the number of CAN devices in the CAN bus chain exceeds 12 pieces.
Systems with CAN ports:
To read data from the CAN sensors, you need a Vutlan monitoring device with one or two CAN ports.